美文网首页ExaSMOC Online
B11. Control Variable View-3 &am

B11. Control Variable View-3 &am

作者: 橡果 | 来源:发表于2017-01-08 21:56 被阅读46次

    提示

    • High Limit 应该 >= Low Limit;
    • SETRANGE LOW≤SETRANGE HIGH
    • SETPOINT LOW ≤ SETPOINT HIGH
    • SETRANGE LOW≥SETPOINT LOW
    • SETRANGE HIGH ≤ SETPOINT HIGH
      如果SET VALUE TYPE(设定值类型)是SET PNT,则只有“SET RANGE HIGH”可编辑,且“SET RANGE HIGH”的值自动复制到“SET RANGE LOW”。
      从R3.06起,CV设定范围有四种类型,Set Range – Zone Control(设定范围-区域控制),Set Point – Setpoint Control(设定点-设定点控制),Low Limit Zone Control(低限区域控制),在CV上只有下限(无上限)和High Limit Zone control(高限区域控制)只有高限(无低限)。在DEF文件中为每个CV定义了SETVALUETYPE。
      即使为每个限制分配了位号名,也会执行上述错误检查。检测到错误时,数据变为Bad。(R4.02)
      **为了将Online Tuning Weight(在线整定权重)反映到控制器,应从控制面板触发在线整定。然后在下一个执行周期得到修改。

    B12经济函数视图

    Economic Function (EF)(经济函数)参数显示在Economic Function(经济函数)面板上。可以在PCTP离线定义多个经济函数。在此面板上,操作员可以选择经济函数并输入控制器的EF参数。
    经济函数面板有“ENG”和“OPE”两种操作模式。以下是ENG模式的窗口。

    查看

    Figure B2.2.9.1 Items/Parameters under EF Panel ENG MODE图B2.2.9.1 EF面板ENG模式下的条目/参数

    条目说明

    各个需要由操作员和工程师输入的条目/参数如下。

    |条目| 描述 |操作员模式| 工程师模式|
    | ------------- |:-------------:| -----:|
    |Common(通用)|
    |Tracking Filter(跟踪滤波) |确定跟踪滤波常数。非负值为可用的,单位是秒。| R |R/W|
    |Economic Function Value(经济函数值) | 所选经济函数的计算值。| R| R|
    |Optimal Value(最优值)| 表示EF在优化期间实现的最佳可能值。为稳态计算值(预测时域终点)。| R |R|
    |Economic Function Selection(经济函数选择) |表示所选的经济函数条目。| R| R|
    |Status(状态)| 指示所选经济函数的状态。 ACTIVE INACTIVE BAD |R |R|
    |EF Common(EF通用)|
    |Economic Function Selection(经济函数选择) |表示所选的经济函数的条目。| R/W |R/W|
    |Function Name(函数名)| 经济函数的唯一位号名。 |R| R|
    |Comments(注释)| EF位号注释。| R| R|
    |Economic Coefficients(经济系数)|
    |Coefficient Name(系数名)| 经济系数的唯一位号名。| R| R|
    |Comment(注释) |经济系数注释。| R| R|
    |Value (值) |经济系数值(Z_Coefficient)。| R/W |R/W|
    |Button(按钮)|
    |Apply Button(应用按钮)| 如前所述。| R/W |R/W|
    |Undo Button(撤销按钮) |在单击Apply按钮之前取消新输入的参数。然后上一个参数显示为黑色。| R/W |R/W|


    原文:
    TIPS

    • High Limit should be >= Low Limit
    • SETRANGE LOW≤SETRANGE HIGH
    • SETPOINT LOW ≤ SETPOINT HIGH
    • SETRANGE LOW≥SETPOINT LOW
    • SETRANGE HIGH ≤ SETPOINT HIGH
      If the “SET VALUE TYPE is SET PNT then only “SET RANGE HIGH” is editable and value of “SET RANGE HIGH” is copied to “SET RANGE LOW” automatically.
      From R3.06, there are 4 type of CV set range, Set Range – Zone Control, Set Point – Setpoint Control, Low Limit Zone Control with only low limit (no high limit) on CV, and High Limit Zone control with only high limit (no low limit) on CV. SETVALUETYPE is defined in the DEF file for each CV.
      The above error check is also done even when the tag name is assigned to each limit. The data becomes Bad when the error is detected. (R4.02)
      ** In order to reflect Online Tuning Weight to the controller, Online tuning should be triggered from the control panel. Then the modification is reflected at the next execution period.

    B12. Economic Function View

    Parameters of Economic Function (EF) are displayed on the Economic Function Panel. Multiple Economic functions can be defined on PCTP offline. On this panel, operators can select the economic function and enters the EF parameters for the controller.
    Economic Function Panel has two modes of operation, “ENG” and “OPE”. Following are the windows for the ENG modes.

    View

    Description of items

    Various items/parameters need to be entered by operator and engineers are described below.

    | Item| Description | Operator mode| Engineer mode|
    | ------------- |:-------------:| -----:|
    | Common|
    | Tracking Filter | Determines the Tracking Filter Constant. Non-negative value is available. Unit is second.| R | R/W|
    | Economic Function Value| Calculated value of the selected Economic Function. | R| R|
    | Optimal Value| Value indicates the EF’s best possible value to achieve during optimization. Value is calculated for steady state (end of the prediction Horizon)| R| R|
    | Economic Function Selection| Indicates the selected Economic Function Index.| R | R|
    | Status | Indicates the status of the selected economic function. ACTIVE INACTIVE BAD| R| R|
    | EF Common|
    | Economic Function Selection | Indicates the selected Economic Function Index. | R/W| R/W|
    | Function Name | Unique Tag Name of the Economic Function| R | R|
    | Comments | EF Tag comments| R | R|
    | Economic Coefficients|
    | Coefficient Name| Unique Tag Name of Economic Coefficient| R | R|
    | Comment Economic Coefficient Comments| R | R|
    | Value | Economic Coefficient Value (Z_Coefficient) | R/W| R/W|
    | Button|
    | Apply Button| As Explained Earlier| R/W| R/W|
    | Undo Button| Cancel a newly entered parameter before the “Apply” button is clicked. Then previous parameter is displayed in black. | R/W| R/W|


    2017.1.8

    相关文章

      网友评论

        本文标题:B11. Control Variable View-3 &am

        本文链接:https://www.haomeiwen.com/subject/lqlcbttx.html